Maxxis 5過程控制器
概述
The Sartorius Maxxis 5 freely programmable process controller, designed for applications as diverse as Phase, Batching, Filling, IBC, Counting and Truck Weighing. Extensive connectivity options and compatibility with all analogue load cells and the digital Pendeo® load cells as well as platform scales and many more weighing solutions. Maxxis 5
特性
- Process Controller for the automated control of weighing processes with up to four scales
- Wide range of opportunities for flexible integration such as option cards, housings, W&M certification and EX approvals
- DAT, multilingual easy-operation interface, backup function, service reports, simulation
- BASIC application with weighing, check and remote terminal function
- With an additional license: internal alibi memory, OPC server, tilt correction
- Supplied with Ethernet TCP | IP, Modbus TCP, RS232, RS485, USB, SD Card
參數(shù)
Load cell connection
All strain gauge load cells;
6- or 4-wire connection
Load cell supply
12V, short-circuit proof.
External load cell supply possible.
Minimum load impedance
min. 75 Ohm
e.g. 6 load cells with 650 Ohm
or 4 load cells with 350 Ohm
Measuring principle
Measuring amplifier:
Delta-Sigma converter
Measuring time:
min 5 ms – max. 1600 ms
Digital filter for load cell
4th order (low pass), Bessel, Aperiodic
or Butterworth
ATEX Zone 2/22 approved (Option)
Zone 2, IIC T4 /
Zone 22, IIIC T80°C
Ta: -10°C ... +40°C
Approved for FM/CSA Class I Div.2
(Option)
NI / I / 2 / ABCD / T4
Ta = -10°C to +40°C – 2015571; NIFW
ANI / I, II, III / 2 / ABCD / T4
Ta = -10°C to +40°C – 2015571; NIFW
A | D Converter Input range
4,8 nV (appr. 7.5 Mio. div.)
Usable resolution: 0.2 μV/d
Measuring signal: 0 to 36mV
(for * nominal load)
Linearity
< 0,003%
Control outputs
4 relay two way contact
Max. switching voltage 31 V DC | 24 V AC
Max. switching current: 1 A
Control Inputs
Quantity: 4 opto-decoupled inputs
Can be used as 'passive' or 'active'
Voltage
Input (active):
Can be switched via a potential-free contact
Input (passive):
– Logic 0: 0 to 5 V DC or
– open Logic 1: 10 to 28 V DC
External power supply required
Current: <7 mA @ 24 V
<3 mA @ 12 V
Power Supply
100 – 240 VAC, (+10/-15 %), 50 - 60 Hz max.
21 W/44 VA
Optional:
24 VDC, (+/-10 %), max 20 W
Temperature effects
Zero: TK0 m < 0.05 μV/K RTI
Span: TKspan < +/- 4 ppm/K
Environmental conditions
Temperature
W&M: –10 °C to +40 °C
Operation: –10 °C to +50 °C
Storage: –20 °C to +70 °C
Weight
Net: 3 kg
Shipping weight: approx. 4 kg
訂貨型號
Type Description Order Number
Maxxis 5 Process Controller, incl. Ethernet TCP | IP and Modbus TCP
1 × RS232 and 1 × 485 | 422, 1 × USB, 1 × SD Card,
4 × digital input (active or passive optional) and 4 × digital outputs as relay
9405 159 00000
相關型號
Maxxis 4
PR 5900/00 Maxxis 5 Process Controller with options: Panel housing (G1), A | D converter(W1), 110 | 230 V (L0),
BASIC Application (H0), Digital Input passive (DE1)
9405 159 00001
PR 5900/01 Maxxis 5 Process Controller with options: Panel housing (G1), A | D converter(W1), 24 V (L8),
BASIC Application (H0), Digital Input passive (DE1)
9405 159 00011
PR 5900/02 Maxxis 5 Process Controller with options: Table top housing (G2), Rear plate cable glands (L12),
A | D converter (W1), 110 | 230 V (L0), BASIC Application (H0), Digital Input passive (DE1),
Power cable with Euro Plug (EU)
9405 159 00021
PR 5900/03 Maxxis 5 Process Controller with options: Housing with bracket (G3), Rear plate cable glands (L12),
A | D converter(W1), 110 | 230 V (L0), BASIC Application (H0), Digital Input passive (DE1),
Power cable with Euro Plug (EU)
9405 159 00031