30/0.25 | 13.3 | 10.5 | 11.0 | 12.5 | 13.5 | 12.0 | |
2.5 | 49/0.25 | 7.98 | 12.5 | 13.0 | 14.0 | 15.5 | 14.0 |
4 | 56/0.30 | 4.95 | 14.0 | 14.5 | 16.5 | 18.0 | 16.0 |
6 | 84/0.30 | 3.30 | 17.0 | 18.0 | 20.0 | 22.5 | 19.5 |
表5 YZ,YZW型300/500V
標(biāo)稱截面(mm2) | 導(dǎo)體結(jié)構(gòu) | 20℃時(shí)導(dǎo)體電阻 | 電纜外徑參考(mm) | |||||
根/單線直徑mm | 1芯 | 2芯 | 3芯 | 4芯 | 5芯 | 3+1芯 | ||
1.5 | 30/0.25 | 13.3 | 7.2 | 11.5 | 12.5 | 15.5 | 15.0 | — |
2.5 | 49/0.25 | 7.98 | 8.0 | 13.5 | 14.5 | 16.5 | 17.0 | 15.5 |
4 | 56/0.30 | 4.95 | 9.0 | 15.0 | 16.0 | 18.0 | 19.5 | 17.5 |
6 | 84/0.30 | 3.30 | 11.0 | 18.5 | 20.0 | 22.0 | 24.5 | 21.0 |
10 | 84/0.40 | 1.91 | 13.0 | 24.0 | 25.5 | 28.0 | 31.0 | 26.5 |
16 | 126/0.40 | 1.21 | 14.5 | 27.5 | 29.5 | 32.0 | 35.5 | 30.5 |
25 | 196/0.40 | 0.780 | 16.5 | 31.5 | 34.0 | 37.5 | 41.5 | 35.5 |
35 | 276/0.40 | 0.554 | 18.5 | 35.5 | 38.0 | 42.0 | — | 38.5 |
50 | 396/0.40 | 0.386 | 21.0 | 41.0 | 43.5 | 48.5 | — | 46.0 |
70 | 360/0.50 | 0.272 | 24.0 | 46.0 | 49.5 | 55.0 | — | 51.0 |
95 | 475/0.50 | 0.206 | 26.0 | 50.5 | 54.0 | 60.5 | — | 55.0 |
120 | 608/0.25 | 0.161 | 28.5 | — | 59.0 | 65.5 | — | 59.0 |
150 | 756/0.50 | 0.129 | 32.0 | — | 66.5 | 74.0 | — | 66.0 |
185 | 925/0.50 | 0.106 | 34.5 | — | — | — | — | — |
240 | 1221/0.50 | 0.0801 | 38.0 | — | — | — | — | — |
六、交貨要求
1、成圈100M,成盤應(yīng)大于100M;
2、短段電纜不小于10M,短段電纜的交貨數(shù)量不超過交貨總長度10%,且每個(gè)包裝件應(yīng)不超過五段;
3、根據(jù)雙方協(xié)議允許任何長度的電纜交貨,長度誤差為±0.5%;
4、用戶對(duì)產(chǎn)品有阻燃特性要求,在合同中需另補(bǔ)充協(xié)議。